The DAPPRA DR Series is a classic step-shape DIN rail power supply series with plastic housing, widely used in building automation and household control systems due to its Class II isolation level.
Covering 15W to 120W with 5V, 12V, 15V, 24V and 48V outputs, the DR Series combines compact footprint, universal AC input and fanless natural convection cooling. The DR-15 / 30 / 60 / 100 models are Class II double insulated — no grounding connection required.
The DAPPRA DR Series is the classic step-shape plastic-housing DIN rail power supply series. It covers seven power ratings — 15W, 30W, 45W, 60W, 75W, 100W and 120W — with single-output configurations of 5V, 12V, 15V, 24V and 48V DC.
Models DR-15, DR-30, DR-60 and DR-100 are Class II double insulated, meaning they require no grounding connection and are ideal for building automation and household control applications. Models DR-45, DR-75 and DR-120 are General Type with FG/PE terminal for standard industrial control equipment. All models are designed for standard TS35/7.5 or TS35/15 DIN rail mounting.
Engineered for building automation, household control and general industrial power supply applications.
Select the appropriate DR model according to the required output power, output voltage and isolation type.
The DR Series is available in seven power ratings. The DR-15, DR-30, DR-60 and DR-100 are Class II double insulated (plastic-housing step-shape). The DR-45, DR-75 and DR-120 are General Type with FG/PE terminal.
| Model | Output Voltage | Output Current | Output Power | Efficiency |
|---|---|---|---|---|
| DR-15-5 | 5 VDC | 2.4 A | 12 W | 77.0% |
| DR-15-12 | 12 VDC | 1.25 A | 15 W | 84.0% |
| DR-15-15 | 15 VDC | 1 A | 15 W | 83.5% |
| DR-15-24 | 24 VDC | 0.63 A | 15.2 W | 85.0% |
| DR-30-5 | 5 VDC | 3 A | 15 W | 74.0% |
| DR-30-12 | 12 VDC | 2 A | 24 W | 81.0% |
| DR-30-15 | 15 VDC | 2 A | 30 W | 82.0% |
| DR-30-24 | 24 VDC | 1.5 A | 36 W | 83.0% |
| DR-60-5 | 5 VDC | 6.5 A | 32.5 W | 76.0% |
| DR-60-12 | 12 VDC | 4.5 A | 54 W | 82.0% |
| DR-60-15 | 15 VDC | 4 A | 60 W | 83.0% |
| DR-60-24 | 24 VDC | 2.5 A | 60 W | 84.0% |
| DR-100-12 | 12 VDC | 7.5 A | 90 W | 87.0% |
| DR-100-15 | 15 VDC | 6.5 A | 97.5 W | 87.0% |
| DR-100-24 | 24 VDC | 4.2 A | 100.8 W | 89.0% |
| Model | Output Voltage | Output Current | Output Power | Efficiency |
|---|---|---|---|---|
| DR-45-5 | 5 VDC | 5 A | 25 W | 72.0% |
| DR-45-12 | 12 VDC | 3.5 A | 42 W | 77.0% |
| DR-45-15 | 15 VDC | 2.8 A | 42 W | 77.0% |
| DR-45-24 | 24 VDC | 2 A | 48 W | 80.0% |
| DR-75-12 | 12 VDC | 6.3 A | 76 W | 76.0% |
| DR-75-24 | 24 VDC | 3.2 A | 76.8 W | 80.0% |
| DR-75-48 | 48 VDC | 1.6 A | 76.8 W | 81.0% |
| DR-120-12 | 12 VDC | 10 A | 120 W | — |
| DR-120-24 | 24 VDC | 5 A | 120 W | — |
| DR-120-48 | 48 VDC | 2.5 A | 120 W | — |
Compact step-shape plastic housing designed for space-saving DIN rail mounting. All dimensions in mm, tolerance ±1 mm.
| Width (W) | 25 mm |
| Height (H) | 93 mm |
| Depth (D) | 56 mm |
| Housing | Plastic, step-shape |
| Isolation | Class II |
| Width (W) | 78 mm |
| Height (H) | 93 mm |
| Depth (D) | 56 mm |
| Housing | Plastic, step-shape |
| Isolation | Class II |
| Width (W) | 93 mm |
| Height (H) | 78 mm |
| Depth (D) | 67 mm |
| Housing | Plastic, step-shape |
| Isolation | General Type (with FG/PE) |
| Width (W) | 55.5 mm |
| Height (H) | 125.2 mm |
| Depth (D) | 100 mm |
| Housing | Metal / Plastic, step-shape |
| Isolation | General Type (with FG/PE) |
| Width (W) | 100 mm |
| Height (H) | 93 mm |
| Depth (D) | 56 mm |
| Housing | Plastic, step-shape |
| Isolation | Class II |
| Width (W) | 63 mm |
| Height (H) | 125.2 mm |
| Depth (D) | 113.5 mm |
| Housing | Metal, step-shape |
| Isolation | General Type (with FG/PE) |
The DR Series supports DIN rail mounting with specific ventilation clearance and orientation requirements for reliable operation.
DR-15: input terminals at the bottom, output at the top. DR-30 / 60 / 100: input terminals on the right, output on the left. DR-75 / 120: input terminals at the bottom, output at the top. Other orientations are not allowed.
Always allow good ventilation clearances around the unit: 5 mm left and right, 40 mm above and 20 mm below, to prevent overheating. When the adjacent device is a heat source, keep 10–15 cm clearance.
Admissible DIN rail: TS35/7.5 or TS35/15. Tilt the unit slightly rearwards, fit over the top hat rail, slide it downward until it hits the stop, press against the bottom for locking, then shake slightly to check the locking action.
DR-15 / 30 / 60 / 100 are Class II double insulated and require no grounding connection. DR-45 / 75 / 120 have FG terminal and must be connected to PE (Protective Earth).
Maximum operating temperature: 50°C for DR-15 / DR-30; 40°C for DR-60 / DR-100; 45°C for DR-45 and DR-120-24/48; 35°C for DR-120-12; 38°C for DR-75-12. Do not install near fire sources or high ambient temperature locations.
Install the unit only in a pollution degree 2 environment — typically dry, well-ventilated locations such as control cabinets. Do not install in places with high moisture or near water.
The DR Series operates with free air convection cooling and requires adequate ventilation clearance. Do not install in orientations other than the recommended mounting position for each model.
Use copper wire only and ensure all strands of each stranded wire enter the terminal connection and the screw terminals are securely fixed to prevent poor contact.
| Terminal | Pin | Assignment |
|---|---|---|
| TB1 | 1 | AC/N |
| TB1 | 2 | AC/L |
| TB2 | 3, 4 | DC OUTPUT +V |
| TB2 | 5, 6 | DC OUTPUT -V |
| TB2 | 7 | LED indicator |
| TB2 | 8 | +V ADJ |
Class II models have no FG terminal — no grounding connection is required. Refer to the DR-30 spec for pinout details; DR-15 has front-panel terminals.
| Terminal | Pin | Assignment |
|---|---|---|
| TB1 | 1 | AC/L |
| TB1 | 2 | AC/N |
| TB1 | 3 | FG (Frame Ground / PE) |
| TB2 | 4, 5 | DC OUTPUT -V |
| TB2 | 6, 7 | DC OUTPUT +V |
| TB2 | 8 | LED indicator |
| TB2 | 9 | +V ADJ |
| Terminal | Pin | Assignment |
|---|---|---|
| TB1 | 1 | FG (Frame Ground / PE) |
| TB1 | 2 | AC/N or DC+ |
| TB1 | 3 | AC/L or DC- |
| TB2 | 1, 2 | DC OUTPUT +V |
| TB2 | 3, 4 | DC OUTPUT -V |
Note: The DR-75 TB2 pin order is +V first, -V second — opposite to DR-45. Verify the terminal label before wiring.
| Terminal | Pin | Assignment |
|---|---|---|
| TB1 | 1 | FG (Frame Ground / PE) |
| TB1 | 2 | AC/N or DC+ |
| TB1 | 3 | AC/L or DC- |
| TB2 | 1, 2 | DC OUTPUT +V |
| TB2 | 3, 4 | DC OUTPUT -V |
Note: The DR-120 TB2 pin order is +V first, -V second — opposite to DR-45.
The FG pin on General Type models (DR-45 / 75 / 120) must be connected to PE (Protective Earth). Both -V pins and both +V pins should be connected to their respective output wires to prevent excessive current stress on a single contact.
| AWG | Rated Current | Cross-section |
|---|---|---|
| 18 | 0–6 A | 0.75 mm² |
| 16 | 6–10 A | 1.00 mm² |
| 14 | 13–16 A | 1.52 mm² |
| 12 | 16–25 A | 2.5 mm² |
Use stranded copper wire only. Current each wire carries should be de-rated to 80% of the current suggested above when using 5 or more wires connected to the unit. Use wires that can withstand temperatures of at least 80°C, such as UL1007. Maximum allowable wire cross-section for DR-45 terminal is 12AWG / 2.5 mm².
| Model Group | Torque | Stripping Length |
|---|---|---|
| Class II (DR-15/30/60/100) | 5 kgf-cm (4.4 Lb-in) | 7 mm (0.275″) |
| DR-45 | 5 kgf-cm (4.4 Lb-in) | 5 mm (0.197″) |
| DR-75 / DR-120 | 10 kgf-cm (9 Lb-in) | 5 mm (0.197″) |
Recommended screwdriver: 3 mm slotted type for Class II models; 4 mm slotted type for DR-45.
| Model | Fuse | C16 | D16 |
|---|---|---|---|
| DR-15 | T2A/L250V | 19 | 22 |
| DR-30 | F2A/L250V | 7 | 15 |
| DR-45 | T2.5A/L250V | 6 | 13 |
| DR-60 | F3.15A/L250V | 3 | 7 |
| DR-75 | T2.5A/L250V | 6 | 11 |
| DR-100 | F3.15A/L250V | 3 | 6 |
| DR-120 | F4A/H250V | 5 | 7 |
Maximum number of DR PSUs that can be connected to a circuit breaker at 230V. For continued protection against risk of fire, replace only with the same type and rating of fuse.
The actual wiring should follow the wiring diagram provided in the DR Series installation manual. Use copper wire only and ensure all strands enter the terminal connection securely.
Read and follow all safety instructions before installing, wiring, maintaining or modifying the DR Series power supply.
Note: Pollution Degree 2 applies where there is only non-conductive pollution that might temporarily become conductive due to occasional condensation. Generally refers to dry, well-ventilated locations, such as control cabinets.
The DR Series is suitable for building automation, household appliance control, industrial control systems and general commercial power supply applications.
Browse all DR Series DIN rail power supply products, or return to the Industrial Power Supply category page.
The DAPPRA DR Series is a classic step-shape DIN rail power supply series. It covers 15W to 120W with 5V, 12V, 15V, 24V and 48V single-output configurations. The DR-15, DR-30, DR-60 and DR-100 models feature Class II double insulation (no grounding required).
The DR-15, DR-30, DR-60 and DR-100 models are Class II double insulated with plastic-housing step-shape design and require no grounding connection. The DR-45, DR-75 and DR-120 models are General Type with FG/PE terminal.
Most DR Series models support a universal AC input range of 85–264 VAC (single phase) or 120–370 VDC. The DR-120 uses selectable 88–132 VAC / 176–264 VAC input by switch.
The DR Series offers 5V, 12V, 15V, 24V and 48V output options depending on the model. Not every power rating offers all voltages.
Efficiency ranges from 72% to 89% depending on the model. DR-75 achieves 76% (12V), 80% (24V) and 81% (48V). The DR-100 achieves up to 89% efficiency.
The DR-15 has a no-load power consumption below 0.5W, and the DR-100 has a no-load power consumption below 1W.
The maximum operating temperature is 50°C for DR-15 and DR-30, 40°C for DR-60 and DR-100, 45°C for DR-45 and DR-120-24/48, 35°C for DR-120-12 and 38°C for DR-75-12.
Class II models (DR-15/30/60/100): TB1 has AC/N and AC/L input; TB2 has +V, -V, LED and +V ADJ. General Type DR-45: TB1 Pin 1 = AC/L, Pin 2 = AC/N, Pin 3 = FG; TB2 Pin 4,5 = DC OUTPUT -V, Pin 6,7 = DC OUTPUT +V, Pin 8 = LED, Pin 9 = +V ADJ. DR-75 and DR-120: TB1 Pin 1 = FG, Pin 2 = AC/N or DC+, Pin 3 = AC/L or DC-; TB2 Pin 1,2 = DC OUTPUT +V, Pin 3,4 = DC OUTPUT -V.
The DR Series is certified to UL508, TUV EN60950-1, and complies with EN61000-6-2 industrial immunity level, EN55022 Class B EMC emission and EN61000-3-2 harmonic current standards.
Select the DR model according to the required output power (15W to 120W), output voltage, Class II isolation requirement and available DIN rail mounting space in the control cabinet.